| Flow Meters and Computations | Meter Types: All linear and square law meters supported including: vortex, turbine, magnetic, PD, target, orifice, venturi, v-cone, coriollis and many others. Linearization: Square root, 16 point table or UVC table Computations: Volume, Corrected Volume and Mass. Fluid Computations: Temperature, Density, Viscosity and API 2540 for petroleum. |
| Operating Temperature | 0 °C to 50 °C |
| Storage Temperature | -40 °C to 85 °C |
| Humidity | 0-95% Non-condensing |
| Extended Temperature | Level display flashes to 699 FT 11 15/16 IN Volume display flashes 9999999 if over range |
| Listing Display | UL/C-UL Listed (File No. E192404), CE Compliant, Type: 2 lines of 20 characters, Types: Backlit LCD, Character Size: 0.35” (8.3mm) nominal user programmable label descriptors and units of measure |
| Keypad | Keypad Type: Membrane Keypad with 16 keys |
| Type | NEMA 4X |
| Materials | Plastic, UL94V-0, Flame retardant Bezel: Textured per matt finish |
| Real Time Clock | The Tek-Batch is equipped with a battery backed real time clock with display of time and date. Format: 12 or 24 hour time display; Day, Month, Year, date display |
| Power Input | The factory equipped power option is internally fused. An internal line to line filter capacitor and MOV are provided for added transient suppression. 110 VAC Power: 85 to 127 Vrms, 50/60 Hz 220 VAC Power: 170 to 276 Vrms, 50/60 Hz DC Power: 2 VDC (10 to 14 VDC), 24 VDC (14 to 28 VDC) Power Consumption: AC: 11.0 VA (11W), DC: 300 mA max. |
| Accuracy | 0.02% FS at 20 ° C |
| Ranges | Voltage: 0-10 VDC, 0-5 VDC, 1-5 VDC, Current: 4-20 mA, 0-20 mA |
| Basic Measurement Resolution | 16 bit |
| Update Rate | 4 updates/sec |
| Automatic Fault Detection | Signal over/under-range, Current Loop Broken |
| Calibration | Software Calibration (no trimmers) and Auto-zero Continuously |
| Extended Calibration | Learns Zero and Full Scale of each range using special test mode. |
| Fault Protection | Reverse Polarity: No ill effects Over-Voltage Limit: 50 VDC Over voltage protection Over-Current Protection: Internally current limited protected to 24VDC |